SNR-UPS-ONRT-2000-XL48

SNR-UPS-ONRT-2000-XL48

$ 639.00
UPS On-Line SNR ELEMENT II series 2000VA/2000W (PF-1.0), 1ph+N+PE (220-240V), 48V (DC), without built-in batteries (charge current 12A), color LCD display, USB/RS232/INTELLIGENT SLOT, RJ-45, REPO, output sockets: 8 x IEC-320 C13, Rack/Tower, height 2U.

Technical Specifications

  • Type of UPS Rackmount
  • Weight, kg (1) 8,5
  • Operating temperature, °C (1) 0
    40
  • Phase 1
  • Input voltage 162-290V (AC)
  • Battery type Lead-acid (external, ordered separately)
  • Type of UPS (1) On-line
  • Without built-in batteries Available

Product Info

Part number: SNR-UPS-ONRT-2000-XL48

The SNR Element series uninterruptible power supply provides protection for sensitive electrical equipment from common power problems, including power failures, drops, surges, line noise, strong voltage spikes, frequency fluctuations, and harmonic distortion. Power failures can occur at unpredictable times, and the quality of electrical energy can also change over time. Power-related problems are dangerous for IT equipment, leading to damage to important data, loss of unsaved work sessions, and equipment breakdown - all of which can result in many hours of downtime and expensive repairs. These UPS units are ideal for protecting servers, telecommunications, network, and industrial equipment. The SNR-UPS-ONRM-2000-XL48 power supply does not have built-in batteries, so 4 batteries must be connected in series to provide autonomous operation, as shown in the diagram.

Scheme of connecting a battery to an uninterruptible power supply (UPS) 15-0001-w400.jpg\" The technology of double voltage conversion ensures complete equipment protection and sine wave output voltage in all operating modes, as well as zero switching time to the battery; output power factor of 0.9; the UPS can work together with generators; an intelligent three-stage charging mode is used to extend battery life; supports ECO mode; \"cold start\" function; standard communication interfaces: one RS-232 communication port, one USB communication port, as well as an internal slot for installing an SNMP card or \"dry\" contacts; function of controlling output socket segments, allowing to disconnect non-critical load in battery mode to increase the autonomous operation time of critical load; for UPS models with built-in batteries, the hot-swappable battery function is available; emergency shutdown function through the remote power-off port (EPO - Emergency Power-off); all important information is displayed on the device screen: the load power and battery status are displayed in dynamic images mode. It is very easy to track the UPS functioning process, when the UPS fails, an error code is displayed on the screen, and the equipment can be restored in the shortest possible time with the help of the fault codes table; the LCD display can change the image orientation according to the type of housing installation: vertically or horizontally; the height of all UPS models in the Element series is only 2U.

Delivery set:

  • User manual
  • CD with software for UPS
  • USB cable
  • Power cable (input and output)
  • RS232 cable
  • Mounting brackets for rack installation
  • Cable for connecting a battery pack for rack installation of uninterruptible power sources
  • We offer universal trays SNR-UPS-RK for purchase separately

Technical Specifications

  • Type of UPS Rackmount
  • Weight, kg (1) 8,5
  • Operating temperature, °C (1) 0
    40
  • Phase 1
  • Input voltage 162-290V (AC)
  • Battery type Lead-acid (external, ordered separately)
  • Type of UPS (1) On-line
  • Without built-in batteries Available
  • Dimension, mm (1) 86,5x440x600
  • COM port Dry contact (optional)
    RS232
    SNMP slot
    USB
  • Maximum number of lines 1
  • Percentage of moisture 0-90% (non-condensing)
  • Number of batteries 4
  • Hour battery rating, A Depend on capacity of battery
  • Battery charging current, A 12
  • Expiratory phase 1
  • Output Voltage 220V (AC) ± 2% (208, 230, 240V (AC) optional)
  • Type and number of outlet sockets IEC 320 C13 x 6
  • Battery voltage 48
  • Input connections IEC320 C20
  • Backup power supply time at 50% load Depend on capacity of battery
  • Output power factor, RF 1
  • Power, VA 2000
  • Power, W 2000
  • Efficiency in mains operation ≥ 87% at 100% power load
  • Intput frequency, Hz 46-54Hz or 56-64Hz (Auto-detect)
  • Output frequency, Hz 50/60Hz ±1Hz